Ensure power is disconnected during installation to prevent damage. 2. Parameter Programming and Setup
Press and release the key. The current Setpoint value flashes on the screen.
If you have an old SB655 C that is failing (e.g., dim display, EE error), do not throw it away until you have read the parameters. Replacements (like the newer Eliwell ID 974 or iDR series) are available, but you need the old settings.
uses a folder-based menu system for both basic operations and advanced configuration. Menu Access ENERGY SB 655CS (SB65023512400)
Decreases values. Can be configured for auxiliary functions like turning on a light. eliwell sb655 c manual
If no evaporator probe is connected, the defrost cycle initiates exactly every dit hours and runs for exactly dEt minutes.
Evaporator defrost temperature probe (Probe 2 / Pb2).
Press to temporarily store the value and return to the parameter code.
This complete guide serves as an in-depth resource and unofficial manual for the Eliwell SB655C. It covers everything from its primary functions and technical specifications to installation, programming, and troubleshooting. Ensure power is disconnected during installation to prevent
Complete Technical Guide and User Manual for the Eliwell SB655 C Controller
1 or 2 configurable voltage-free digital inputs (e.g., door switch, high-pressure alarm). Output Relays: Compressor: 8A, 15A, or 20A (model dependent). Defrost: 8A. Evaporator Fans: 8A. Auxiliary/Alarm: 8A. 2. Installation and Wiring Guidelines
3-digit LED display with automatic minus sign and decimal point Resolution: 0.1°C or 1°C (selectable via parameters)
| Label | Description | Notes | | :--- | :--- | :--- | | | | | | SEt | Temperature Setpoint for the controlled medium. | - | | diF | Differential (Hysteresis). The compressor stops at SEt and restarts at SEt + diF . | Value cannot be zero | | HSE | Maximum allowable Setpoint value. | Prevents user error | | LSE | Minimum allowable Setpoint value. | Prevents user error | | Operating Mode | | | | HC | Regulator operating mode. Set to C for cooling (chiller) or H for heating (heat pump). | Caution: Changing this may require reconfiguring other parameters | | Defrost Settings | | | | tdF | Type of defrost (e.g., Electrical, Hot Gas). | Configure based on system | | EdF | Defrost interval between cycles. | - | | MdF | Maximum duration for a defrost cycle. | Safety cut-off | | Fan Management | | | | FSt | Fan stop temperature (when the evaporator is very cold). | Optimizes system efficiency | | FOn / FOF | Differential temperatures to cycle fans on/off. | - | | Alarm Parameters | | | | ALu / ALL | High and low temperature alarm thresholds. | Defines the acceptable temperature range | | PAL | Delay time for an alarm to be triggered after a threshold is crossed. | Prevents nuisance alarms | The current Setpoint value flashes on the screen
Before programming, understand what you are looking at:
If the parameter matrix becomes corrupted or unmanageable, you can restore factory defaults: Power down the controller. Power up the unit while holding down the key.
: To enter the full menu, press and hold the SET button for more than five seconds until "PA2" appears.
Determines fan behavior during compressor operation. 0 = fans run continuously; 1 = fans cycle on/off with the compressor.
230Vac ±10%, 50/60Hz (depending on the specific model variant)